Mitsubishi Electronics liikkumisen apuväline #NAME? Manuaali

PDF-Manuaalit
96 Sivut Englanti

Mitsubishi Electronics liikkumisen apuväline #NAME?
5
SETTINGS AND PROCEDURES BEFORE
OPERATION
5.1 Q Series Safety Relay Module
5.1.4 Mounting/removal
5 - 6
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
FUNCTIONS
5
SETTINGS AND
PROCEDURES BEFORE
OPERATION
6
TROUBLESHOOTINGAPPENDIX
5.1.4 Mounting/removal
For mounting/removing the Q series safety relay module on/from the base unit, refer to the
QCPU User's Manual (Hardware Design, Maintenance and Inspection) together.
When installing a programmable controller to a control panel or similar, fully consider its
operability, maintainability, and environmental resistance.
(1) Installation position
Keep the clearances shown below between the top/bottom faces of the modules and
the control panel or other parts so that good ventilation is ensured and the modules
can be easily replaced.
* 1: A clearance required when the wiring duct is 50mm or less in height A 40mm or more clearance is
required when the wiring duct is longer.
Figure 5.3 Installation position
*1
Ceiling of the control panel,
wiring duct or any other parts
5mm or more 5mm or more
30mm or more
30mm or more
20mm
or more
Programmable
controller
DoorControl
panel
Sisällysluettelo
Laajenna Kaikki